Description / Abstract:
This guide describes VLF withstand and other diagnostic tests
and the measurements that are performed in the field on
service-aged shielded medium and high-voltage cables rated 5 kV
through 69 kV with extruded and laminated insulation. VLF test
methods utilize ac signals at frequencies less than 1 Hz. The most
commonly used, commercially available, VLF test frequency is 0.1
Hz. Whenever possible, cable systems are treated in a similar
manner to individual cables. Tables are included of the recommended
test voltage levels for installation, acceptance, and maintenance
tests.
Purpose
This guide is intended to provide troubleshooting and testing
personnel with information to test shielded medium- and
high-voltage cable systems rated 5 kV through 69 kV using VLF ac
techniques.